Industrial water filters » Mechanical filters

CAF1000 series automatic pump filters

 

 

 

 

    

     An automatic pump filter installed in the water inlet socket automatically protects the pump from sand and gravel contaminants. In addition, these filters protect the entire water cycle, including cooling towers and thermal converters, from contamination. The entire water system and the pump do not stop working, which prolongs their service life and ensures efficient water supply.

     The special design of the pump protects the entire system and pump from organic and inorganic contaminants. An automatic pump filter can be connected to the pump outlet. This system is connected under water (pool, river, water tank, etc.).

 

 

 

 

 

 

 

 

Operation principle

 

     When water enters the filter, organic and inorganic fragments and solid particles are trapped. In this way, the pump and other equipment are protected against clogging and damage, water circulation efficiency is improved, energy and maintenance costs are reduced.

 

     The filter has a self-cleaning function: manually adjustable valve (12), adjustable flushing current with hydraulic actuator (13) and self-cleaning component (4). 

 

 

 

 

  1. Pump filter
  2. Adapter
  3. Manual filter
  4. Self-cleaning component
  5. Sprayer
  6. Filter inner surface
  7. Pump outlet
  8. Rinse aid outlet
  9. Rinse aid inlet
  10. Pressure sensor
  11. Check valve
  12. Manually controlled valve
  13. Hydraulic drive

 

Applications

 

  • Industry: protection of swimming pool pumps, circulating fluid pumps, sewage pumps, etc.
  • Housing and public utilities: protection of pumping stations pumps, sewage treatment pumps, etc.
  • Agriculture: protection of pumps for lake, river and sea water.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Technical data

Model

Outlet DN, mm

Diameter Ø DN, mm

Height, H

Water flow at 1.2 mm, m3/h

Water flow at 2.5 mm, m3/h

Weight, kg

CAF 1004

100

560

52

80

100

25

CAF 1006

150

560

67

150

190

35

CAF 1008

200

560

87

300

380

45

CAF 1010

250

830

79

500

630

60

CAF 1012

300

830

79

700

880

70

CAF 1014

350

1160

1029

1100

1000

120

CAF 1016

400

1160

1029

1400

1380

130

CAF 1018

450

1375

1032

1750

2180

190

CAF 1020

500

1375

1032

2200

2750

210

Minimum operating pressure: 0.15 Mpa

Filter material: 304 stainless steel

 

 

Wash water consumption

 

 

Filter selection

 

When selecting the automatic pump filter, it is important to pay attention to the following:

Pump water flow rate;

  • Pump inlet diameter;
  • The number of solid particles;
  • Accuracy;
  • Pump operating pressure;
  • Installation location.

 

Installation